GN19-12 indoor HV disconnect switch applies to power system of rated voltage below 12KV, AC 50/60Hz. It is equipped with CS6-1 manual-operating mechanism and is used to break and make circuit under no-load. There are additional pollution type, high-altitude type and electrified display.
Model No | Rated voltage | Rated current (A) | Rated short time withstand current(4s) KA | Rated peak withstand current KA |
GN19-12/400-12.5 | 12kV | 400A | 12.5 | 31.5 |
GN19-12/630-20 | 12kV | 630A | 20 | 50 |
GN19-12/1000-31.5 | 12kV | 1000A | 31.5 | 80 |
GN19-12/1250-12.5 | 12kV | 1250A | 31.5 | 80 |
GN19-12C/400-12.5 | 12kV | 400A | 12.5 | 31.5 |
GN19-12C/630-20 | 12kV | 630A | 20 | 50 |
GN19-12C/1000-31.5 | 12kV | 1000A | 31.5 | 80 |
GN19-12C/1250-31.5 | 12kV | 1250A | 31.5 | 80 |