Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
a).Does not have the pollution, does not have the fire and the explosion hazard;
B) longer machinery, electrical life, electrical life 6,000;
C) moves overhauls the quantity to be extremely few, achieves nearly does not need to service;
D) may frequently operate;
E) holds the drive mechanism to be possible to select the CT19BN spring to hold the drive mechanism or the CD10 III electromagnetism holds the drive mechanism; This product conforms to GB1984-89 "A.c. high voltage Circuit breaker" and DL402-91 "A.c. high voltage Circuit breaker Ordering Engineering factor" request.
Zhejiang Xiya Electric Equipment Co., Ltd. was founded in 1995, invest about more than RMB 10 million, one of the high-tech enterprise of production, sales, research and development. The company covers a land area of 5 acres. We are specialized in manufacturing dropout fuse cutout, zinc oxide arrester, isolating switch, lightning protection insulator, composite insulator, bushing and surge protector and complete sets of products. Our company has been elected to Two-Net reconstructing enterprise by Nation Economy & Trade Committee.
Serial number |
Name |
Unit |
Value |
|
1 |
Rated voltage |
kV |
40.5 |
|
2 |
Fixed insulation level |
Labor frequency voltage ( 1min ) |
95 |
|
Lightning surge voltage (peak value) |
185 |
|||
3 |
Nominal frequency |
Hz |
50 |
|
4 |
nominal currents |
A |
1600,2000 |
|
5 |
fixed single condenser banks drop-out currents |
400 |
||
6 |
fixed short-circuit drop-out current |
kA |
25 31.5 |
|
7 |
7 fixed short-circuits the pass to gather the electric current (peak value) |
63 80 |
||
8 |
fixed peak values electric currents |
63 80 |
||
9 |
fixed short-time electric currents (4s) |
25 31.5 |
||
10 |
The fixed out of phase short-circuits the drop-out current |
21.7 27.4 |
||
11 |
Fixed operation sequence |
0-0.3s-CO -180s-CO |
||
12 |
minute floodgates time (rated voltage) |
s |
≤ 0.06 |
|
13 |
Gathers Floodgate time (rated voltage) |
≤ 0.1 |
||
14 |
Mechanical life |
6000 |
||
15 |
Electricity life |
Opens breaks the nominal current |
6000 |
|
Opens breaks fixed short-circuits the drop-out current |
20 |
|||
16 |
Moves, the static contact permission attrition thickness |
mm |
3 |
Serial number |
Name |
Unit |
Value |
1 |
Contact travelling schedule |
mm |
25 |
2 |
Overtravel |
8 |
|
3 |
Alternates with the center distance |
460 ± 2.5 |
|
4 |
Oil cushion power stroke |
15 |
|
5 |
Averageg gathers floodgate speed |
m/s |
0.8 ± 0.2 |
6 |
After evenly divided equally the floodgate speed (just to divide in 18mm contact travelling schedule average velocity) |
1.8 ± 0.2 |
|
7 |
Main return route resistance |
μΩ |
≤ 100 |
8 |
The contact gathers floodgate bounces the time |
ms |
≤ 3 |
9 |
Three coincides, divides the floodgate No Same time |
≤ 2 |