SF6 gas insulated load break switch is outdoor type pole mounted 11KV 3 phase 50/60Hz ac SF6 insulated. The make and break switching operation can be performed in " ON/ OFF LOAD" condition,used for the sectionalization of HT network.
The assembly of Sf6 insulated load break switch is supplied as a single unit with single pole mounting arrangement and can be manually operated. The unit can facilitate the installation of the assembly on both sides (left or right) of the pole to operate and install the operating handle in accordance with the site conditions.
Tank case material is stainless steel: tank case is designed for its maximum robustness so that at a maximum bursting pressure of the tank,switching operaion is not disturbed. Moreover, its minimum welding line of stainless steel tank case results in minimum corrosion
The insulation of load break switch is SF6 gas,meets the requirement of IEC60376 latest application. To maintain the insulating capacity of SF6 gas during the service life of switch, a moisture and de-composed gas obsorber contain in the tank
The enclosure is sealed for life and meets "Pressurized sealed system" criteria in conformity with the standard IEC62271-1.
SF6 load break switch is fitted with safety bursting mumbrane located in the safest part of the tank. It will avoid any damage to the operator in case of an overpressure (internal arc). opening the membrane before the tank or bushing are destroyed.
A low pressure gauge is provided at the bottom of tank which can be visible /readable by operator along with the low pressure lockout mechanism, which interlocks/ prevents the electrical and mechanical operation if the gas pressure is low.
The polymer insulators are made of HTV (High Temperature Vulcanization) silicone rubber polymer having excellent hydrophobic properties so as to meet the electrical and mechanical characteristics of international standards IEC61109,60383 & 62271 (Latest edition). The insulators is grey color and free from cracks and any other visible coating defects.
The mechanical and electrical characteristics of the silicon rubber insulator is as under:
Main technical datas:
Climatic Conditions:
1 | Item | Unit | 12/24 | ||
2 | Rated voltage KV Rated frequency | Hz | 50/60 | ||
3 | Rated insulation level (charged SF6 gas 0.05MPa/20°C) | Lightning impulse withstand voltage (peak) | Phase to phase , phase to earth | kV | 75/125 |
Across open contacts | 85/145 | ||||
1 min P.F withstand voltage | Phase to phase , phase to earth | 42/64 | |||
Across open contacts | 48/79 | ||||
Raining withstand voltage test | 34/50 | ||||
4 | Insulation level under zero gauge pressure 1 min P.F withstand voltage | kV | 30 | ||
5 | Rated current | 630 | |||
6 | Rated load breaking current at 0,05MPa /20°C) | A | 630 | ||
7 | Breaking current at zero gauge pressure | 630 | |||
8 | Rated short-circuit making current | kA | 50 | ||
9 | Rated short-time withstand current / duration | kA/s | 20/4 | ||
10 | Rated peak withstand current(peak) | kA | 50 | ||
11 | Rated cable charging breaking current | A | 25 | ||
12 | Rated line charging breaking current | 1.5 | |||
13 | Rated loop breaking current | 630 | |||
14 | Breaking times of rated load breaking current | times | 100(E3 class) | ||
15 | Rated SF6 gas pressure | Mpa | 0.05±0.01 | ||
16 | Main loop resistance for each phase | μΩ | ≤120 | ||
17 | Relative gas leakage rate | yearty | ≤1% | ||
18 | SF6 gas moisture content | Delivery ex-factory value | ppm | ≤150 | |
Switch operating value | ≤300 | ||||
19 | Mechanical life | times | 5000(M2 class) | ||
20 | Contact gap | mm | 47 ±2 | ||
21 | Contact over-travel | 17±2 | |||
22 | Average opening speed | m/s | 1.2±0.2 | ||
23 | Average closing speed | 0.6±0.2 | |||
24 | Closing time | ms | 25-60 | ||
25 | Opening time | 18-45 | |||
26 | Rated operating voltage | V | DC220,AC220 | ||
27 | Rated power for energy storage motor | W | 40 | ||
28 | 1 min P.F withstand voltage for secondary loop | kV | 2 | ||
29 | Phase-to-phase spacing | mm | 235±1.5/340±1.5 | ||
30 | Net weight | kg | 125/155 |