Customization: | Available |
---|---|
Application: | Construction, Overhead, Underground, Industrial, Power Station, Telecommunication, Computer, Car |
Voltage: | High Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
LW36A-72.5 open combinations are new type products which developed by our company. Compared with foreign similar products, the product can meet the needs of domestic electric power market. Our company can according to the different needs of users, not only design the layout form of flexible and varied, and can be Practice the whole substation a devices (including interval bearing busbar, tower, etc.) and the secondary equipment of general contracting. LW36A-126 open combination electric appliance, advanced structure, good performance, technical parameters can completely satisfy the requirements of GB and IEC standards. The product has both closed-end structure tight combination Gather together, cover an area of an area small features, and has the advantages of open electric price is cheap, convenient maintenance, compared to the conventional power station to reduce its covers an area of about 60%, especially for city network and substation mountainous area and industrial and mining enterprises to choose.
No. |
Item |
Unit |
Data |
|
1 |
Rated voltage |
KV |
72.5 |
|
2 |
Rated current |
A |
3150 |
|
3 |
Rated frequency |
HZ |
50/60Hz |
|
4 |
First pole to clear factor |
|
1.5 |
|
5 |
Rated short circuit breaking current |
KA |
31.5 |
|
6 |
Rated short-circuit current (peak) |
KA |
100 |
|
7 |
Rated short-circuit withstand current |
KA |
40 |
|
8 |
Rated power frequency withstand voltage(1min) |
Phase to earth |
KV |
K·230 |
Phase to phase |
K·(230+70) |
|||
9 |
Rated lightning impulse withstand voltage |
Phase to earth |
KV |
K·550 |
Phase to phase |
K·(550+103) |
|||
10 |
Rated peak withstand current |
KA |
100 |
|
11 |
Rated out of step current |
KA |
10 |
|
12 |
Near fault current |
KA |
90%1K |
|
13 |
Electrical life of rated short circuit breaking current |
times |
20 |
|
14 |
Rated short circuit duration |
s |
4 |
|
15 |
Rated line charging close current |
A |
50 |
|
16 |
Rated operation sequence |
|
O-0.3s-CO-180s-CO |
|
17 |
Main circuit resistance |
μΩ |
≤35 |
|
18 |
Rated SF6 gas pressure |
MPa |
0.5 |
|
19 |
SF6 gas leakage rate |
ppm |
≤0.5 |
|
20 |
Moisture content of SF6 gas (V/V) |
|
≤150 |
|
21 |
Mechanical life |
times |
6000 |
|
22 |
Electric distance |
Phase to earth |
mm |
3906/3150 |
Phase to phase |
3906/3150 |
|||
23 |
Each filled with SF6 gas quality |
kg |
6 |
|
24 |
Quality of each circuit breaker |
kg |
1200 |