Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ZN85-40.5 type indoor high voltage indoor vacuum circuit-breaker is used for switchgear KYN61-40.5(Z), it is most new type of power supply and distribution equipment. This product is accordance with GB1984-2003 stand. This series include: Vacuum circuit breaker truck, isolation truck and fuse truck.
Structural Characteristics:
1. This vacuum circuit breaker adopts compound insulation; it can meet air distance and creepage under normal run condition, and it effectively reduces the dimension of VCB, the overall arrangement is reasonable and simple, with aesthetic appearance.
2. The operating mechanism is especially newly designed for this VCB; the outlet curve has good adaptation with requirements of vacuum interrupters. It has high reliable with characteristics of long life and easy maintenance and free-maintenance for operating mechanism.
3. This truck adopts screw rod nut push-in mechanism which can realize easy pushing-in or pushing-out of panel; compulsive mechanical interlock way is adopted; meet the Five Preventions function; suitable for varies site and the working sites which have rigorous run condition
No. | Item | Units | Technical parameters | ||||
1 | Rated voltage | KV | 40.5 | ||||
2 | Rated current | A | 1250 | 1600 | 2000,2500 | ||
3 | Rated short-circuit breaking current | KA | 25 | 31.5 | 25 | 31.5 | |
4 | Dynamic current(peak) | KA | 63 | 80 | 63 | 80 | |
5 | 4S Termal current | KA | 25 | 31.5 | 25 | 31.5 | |
6 | Rated short-circuit closing current(peak) | KA | 63 | 80 | 63 | 80 | |
7 | Rated short-circuit breaking current breaking number | Times | 20 | ||||
8 | Rated operating sequence | O-0.3s-CO-180s-CO | |||||
9 | Rated insulation level | 1 min Frenquency voltage | KV | 95 | |||
Lightening Impulse voltage tolerance(peak) | 185 | ||||||
10 | Mechanical life | Times | 10000 | ||||
11 | Rated single capacitor device ON-OFF current | A | 630 | ||||
12 | Rated single back-to-back capacitor device current | A | 400 | ||||
13 | Rated voltage electrical energy storage | V | AC,DC:110;120 | ||||
14 | Energy storage power Rating | W | ≤ 230 | ||||
15 | Electrical Energy Storage Energy storage time | S | ≤ 15 | ||||
16 | Hop Tripping coil rated voltage | V | AC,DC:110;120 | ||||
17 | Hop Tripping coil rated current | A | 1.05(110V),0.96(220V) | ||||
18 | Contactor opening distance | mm | 20±2 | ||||
19 | Contactor contract trip | mm | 7.5±1.5 | ||||
20 | At the different period of three consistency | ms | ≤ 2 | ||||
21 | Contact closing bounce time | ms | ≤3 | ||||
22 | Leading electrical circuit resistance (excluding contactor arm) | μΩ | ≤40 |