Customization: | Available |
---|---|
Breaking Capacity: | 20 |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ZW32 type high voltage Outdoor 3 pole Vacuum Capacitor Switch(auto circuit recloser) it is a long mechanical life vacuum switch that provides an operational life of over 100,000 (30,000 open / close) maintenance-free operations. Use ZW32 will result in substantial savings from reduced maintenance and maximized bank uptime and will also improve power quality. It complies with standards ANSIC37.66 and China standard. For this vacuum switch, ZW32-40.5 availiable has 33KV 35KV 36KV 38KV 40.5KV. It has motorized spring type & magnetic actuator (with control box) type.
33KV Outdoor Vacuum Circuit Breaker Installation dimensions:
How to wire with vacuum switch
Make sure the end -user follow below diagram to connect the junction box to ZW32 vacuum switch. Junction box is self-power supply controller
Before employ switch for H.V.line, please make sure each cable connector is correct connection.
Please push each A.B.C phase switch button to check if connection in good condition. The proper work is each phase electric control is corresponding correct phase switch.
Rated voltage, kV |
30 -40.5 |
|
Max. working voltage, kV |
40.5 |
|
Rated current, not less than, A |
630A / 1250A /1600A |
|
Rated breaking current, not less than, kA |
20 |
|
Electrical dynamic withstand current, kA |
51 |
|
Operation times |
30000 |
|
Heating withstand current (during 3 seconds/this parameter must not be as 1 sec) , not less than, kA |
20 |
|
Open, close reserve, not less than - By rated current, Close-Open action - By breaking current, Close-Open action |
30000 25 |
|
Breaking own period, not more than, ms |
45 |
|
Full breaking period, not more than, ms |
55 |
|
Close own period, not more than, ms |
60 |
|
Testing voltage of lightning impulse, kV |
190 |
|
1 min testing voltage by voltage with production frequency, kV |
95 |
|
Cycle of recloser |
O-0.02S-C-0.1S |
|
Max amount of close and open cycle within 1 hour, not less than |
100 |
|
Ambient environmental condition performance |
Dedicated to work for outdoor and cold weather |
|
Upper limit of ambient relative moisture when air temperature is at 25°C |
|
|
Ambient environmental min temperature,°C (It must be approved by test) |
-50 |
|
Ambient environmental max temperature,°C (It must be approved by test) |
+55 |
|
Environmental condition, not less than |
Above 1500 m from sea altitude |
|
Protection degree of drive external main body |
IP54 |
|
Penetration length of external insulating, mm, not less than |
1700 |
|
Permissible environmental wind amount when no icing-not more than |
40 m/s |
|
Permissible environmental wind amount of wire iced period (Icing wall thickness is till 20 mm), not more than |
15 m/s |