This technical specifications is suitable for ZN63(VS1)-12/ indoor AC medium voltage vacuum circuit breakers with spring operation mechanism. It is used for 3-phase 50/60Hz 12KV electrical system for protection & controlling.
This technical condition specifies the ZN63(VS1)-12/ indoor AC medium-voltage vacuum circuit breaker in terms of service conditions, rated parameters, technical requirements, test methods, inspection rules and requirements for packaging, transportation and storage, etc .In addition to meet the national standard GB1984-2014 "AC high-voltage circuit breaker", the circuit breaker shall also meet the requirements of this technical condition.
No. | Required | unit | value | |||
1 | Rated Voltage | kV | 12 | |||
2 | Rated Frequency | Hz | 50 | |||
3 | Rated lightning impulse withstand voltage(peak) | kV | 42 | |||
4 | Rated power frequency withstand voltage (1s)(Effective) | kV | 75 | |||
5 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 |
6 | Rated current | A | 630,1250 | 630,1250,1600 | 1250,1600 | 1600,2000 |
2000,2500 | 2500,3150 | |||||
7 | Rated peak withstand current | kA | 50 | 63 | 80 | 100 |
8 | Rated short time withstand current | kA | 20 | 25 | 31.5 | 40 |
9 | Rated short circuit continuous time | s | 4 | |||
10 | Rated short-circuit on/off current | kA | 50 | 63 | 80 | 100 |
11 | Percentage of the d c component of the rated short-circuit breaking current | % | 35 | |||
12 | Rated operation sequence | O-0.3s-CO-180s-C | ||||
O-180s-CO-180s-C(40kA) | ||||||
13 | Rated single/back-to-back capacitor bank breaking current | A | 630/400 | 630/400 | 630/400 | 800/400 |
14 | Rated short-circuit current breaking | times | 50 | 50 | 50 | 30 |
15 | Mechanical life | times | 10000 | |||
16 | Rated opening/closing operation voltage | V | AC/220 D C/220 | |||
17 | Rated voltage of energy storage motor | V | AC/220 D C/220 | |||
18 | Power frequency withstand voltage of secondary circuit | V | 2000 |
ZN63-12(VS1)high voltage vacuum circuit breaker is the indoor switchgear with 12kV rated voltage, three phase AC 50HZ. It acts as the electrical protective and control device in the power system, especially applicable to locations that need frequent operating in rated current or under repeatedly on/off shortcircuit current.
This breaker was designed as a unit which gathering actuator and circuit breaker main body. It can be used for fixed mounting unit, also can be constituted as a withdrawable unit through outfit dedicated advancing mechanism. Corresponding interlock can be increased to meet the needs of XGN2, GG1A and other fixed cabinets. Simultaneously, it can coordinate with the KYN28A-12(GZS1) middle-arranged manual-driven switchgear or XGN-fixed switchgear as well.
Usual service condition
Ambient temperature: not higher than +40 °C, not less than -10°C (at -30 °C to allow storage and transportation).
Altitude: not exceed 1000m.
Relative humidity: daily average of not more than 95%,saturated vapor pressure on the average of not more than 2.2 × 10-3MPa, On average not more than 1.8 × 10-3MPa.
Earthquake intensity: not more than eight.
No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.