LW36-40.5 Outdoor AC 50HZ sulfur hexafluoride circuit breakers for three-phase power system of outdoor equipment, forindustrial and mining enterprises, power plants and substations for control and protection. The product can be frequentoperation can be used as contact breakers and meet the capacitor, circuit breaker with reactor group. Containing a cuπent transformer for measurement and protection, can directly replace SW2-35-type breaker, with various models of transition support alternative multi-oil circuit breakers, 35kV power system is the ideal non-oil circuit device.
Note: The circuit breaker in the hot standby state, the fracture City Road side of the arrester must be installed.
LW36-40.5 cirrcuit breaker equipped with the CTl4-A type of AC-D C dual-spring mechanism. 1.3 LW36-40.5-type circuit breakers meet the GB1984 "high voltage circuit breakers" standard.
2 products for the working conditions and environment.
a Altitude: not exceed 3000m;
b. Ambient temperature:-25oC - ten 40oC; ιWind speed: less than 34m Is;
d. Contamination Level IV, porcelain Creepage distance:> 1255mm;
e. No flammable substances, explosion, chemical corrosion and severe vibration. Note: Out of the above requirements, in consultation with the manufacturer by the user.
No. |
Item |
Unit |
Data |
1 |
Rated voltage |
KV |
30, 33, 35, 36, 38 |
2 |
Rated frequency |
Hz |
50/60 |
3 |
Rated current |
A |
630 , 1250 |
4 |
1min power frequency withstand voltage |
KV |
95/118 |
5 |
Lingthning impluse withstand voltage(peak value |
KV |
215 |
6 |
5 min power frequency voltage at zero gas pressure |
KV |
40.5 |
7 |
Rated short circuit breaking current |
KA |
63,80 |
8 |
Rated out-of-phase breaking current |
KA |
8/10 |
9 |
Rated cable(line) charging breaking current(peak) |
A |
31.5 |
10 |
Rated gas pressure |
MPa |
0.4/0.15 (higher current) |
11 |
Main loop resistance |
uΩ |
≤80 |
12 |
Operation sequence |
O-0.3s-CO-180s-CO |
|
13 |
SF6 gas leakage rate(per year) |
% |
≤1 |
14 |
Moisture content(V/V) |
ppm |
≤150 |
15 |
Creepage distance Across the open comtacts Creepage distance To earth |
mm mm |
1256 1256 |
16 |
Mechanical life |
times |
10,000 |