Customization: | Available |
---|---|
Breaking Capacity: | 10ka |
Type: | Current Fuse |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Meet all applicable Standards ANSI/NEMA
Type K and Type T fuse links are made in complete accordance with standards ANSI/NEMA. Other links meet all the standards except those covering time-current characteristics. Time-current characteristics for links other than K and T links are not covered in the ANSI standards.
Meet all applicable Standards ANSI/NEMA
Type K and Type T fuse links are made in complete accordance with standards ANSI/NEMA. Other links meet all the standards except those covering time-current characteristics. Time-current characteristics for links other than K and T links are not covered in the ANSI standards.
Packaging
fuse links come in protective plastic bags with perforations to facilitate quick, easy opening even when lineman's gloves are worn. Each bag remains completely sealed for all-weather protection and keeps the links protected in the line truck's bins.
Type and amperage is printed on each bag, for easy identification.
Materials used
The fusible section of the 1 through 3 ampere Type K links consist of a stainless-steel fuse strain wire; the 6 through 10 ampere, stainless-steel strain wire and a copper-alloy fuse wire; 12 through 100amperes, a stainless steel strain wire and a silver-copper fuse wire; 140 and 200 ampere, a silver -copper fuse wire large enough to serve as both strain and fuse wire.
Twin Pigtail Type K fuse links
The twin pigtail fuse link is convenient to work with and easier to install in the cutout than conventional single pigtail fuse links. The pigtails attach under the clamp with one on each side of the attachment stud.
Technical Parameter Table 1
Melting Speed Ratio |
T type: 10~13 ; K type: 6~8 |
Rated Current |
1, 2, 3, 6, 8, 10, 12, 15, 20, 25, 30, 40, 50, 60, 65, 75, 80, 100, 120, 140, 200A |
Standard |
IEC 60282-2 |
Environmental Conditions |
Ambient Temperature: -30 - +40 Altitude: 3000m Frequency: 50Hz / 60Hz Maximum Wind Speed: 35m/s |
Technical Parameter Table 2
Rated current (A) | Dimensions (mm) | ||||
A | B | C | D | F | |
1-25 | 12.5±0.2 | 19.0 ± 0.2 |
12/24KV: 530-600 36KV: 787 |
2 | 6.5 |
30-40 | 12.5±0.2 | 19.0 ± 0.2 | 3 | 8.0 | |
50-100 | 19.0±0.3 | not applicable | 5 | 10.0 | |
120~200 | 19.0±0.3 | not applicable | 7 | 12.0 |